Precast concrete concepts and acoustic insulation between dwellings

In March 2022, the WTCB published the long-awaited Technical Information Note (TV 281), ‘Acoustic insulation between dwellings’. Based on the performance requirements in the revised acoustic standard for residential buildings, it assesses the acoustic performance of a number of construction concepts. Clear checklists for different construction concepts enable designers to quickly find the information they need to meet the performance requirements.
Regulatory framework
The requirements of the revised standard NBN S 01-400-1 apply to completed buildings. However, they should also be used as a starting point when designing new buildings. The standard defines three performance levels:
- Class C provides users with a minimum level of acoustic protection under normal noise conditions.
- Class B aims for a higher level of acoustic comfort than the baseline performance level of class C.
- Class A provides users with a very high level of acoustic protection. It can therefore also accommodate somewhat higher noise levels, such as those generated by sound systems, TVs and musical instruments.
Class C is the minimum performance level specified in the standard. For terraced houses, class B is the minimum required performance level. The class A or B performance requirements only apply if they have been stipulated by the client or purchaser of the construction project.
The requirements are set out as follows:

Construction concepts
The construction concepts in TV 281 provide an alternative to the complex calculations set out in the NBN EN ISO 12354 series. The resulting acoustic performance of each construction concept was calculated using these calculation standards, supplemented by calculation models developed by the WTCB. Their reliability was checked against a large number of measurements taken on site and in the laboratory.
The construction concepts distinguish between:
- Continuous and discontinuous floor slabs at dwelling-separating walls
- Single-leaf and double-leaf dwelling-separating walls.
For single-leaf walls, most construction concepts include lining walls made from mineral insulation boards (60 mm thick), plasterboard (2 x 12.5 mm thick, fixed to a frame) or gypsum blocks (100 mm thick).
It is important to interrupt the internal cross wall and the façade wall in most construction concepts. Only when using (precast) concrete can the interruption be omitted in some cases.
The construction concepts are described in tables of performance requirements. Acoustic performance is strongly affected by the surface mass (‘mass’) of the floor slab, expressed in kg/m². This is the sum of the mass of the structural floor and any topping, and the mass of the levelling layer beneath the resilient interlayer.
The following table gives possible floor build-ups for achieving the required mass:

Achieving class A is difficult in apartment buildings and column houses. In apartment buildings, it is only possible with continuous floor slabs and single-leaf dwelling-separating walls made from cast-in-situ or precast concrete (190 mm thick), or solid calcium silicate blocks (240 mm thick), together with lining walls. The required floor slab mass is 700 kg/m². There is a slightly wider choice of construction concepts for achieving class A in column houses. In this case, the floor slabs must have a mass of 600 kg/m² or 700 kg/m². For terraced houses, construction concepts with discontinuous floor slabs are the best solution. Even class A can be achieved with a floor slab mass of 300 kg/m.