Cordeel, Temse | New Cordeel headquarters achieves excellent airtightness score

Cordeel set a very high bar for its new headquarters, not only in architectural and functional terms, but also in energy performance…
In building its new headquarters, Cordeel set a very high bar not only in architectural and functional terms, but also in energy performance. The first step towards an energy-efficient building is to ensure that heat cannot escape or cold air enter when this is not wanted. Mission accomplished: the blower door test showed that the cantilevered beam volume achieved a very favourable airtightness score of 3.6 m³/h.m² (v50).
The blower door test at ‘Kantoorvilla Cordeel’ took place in mid-May. It was carried out by specialist Metifix (formerly EPB Lipa), which also specialises in EPB reporting, airtightness testing and a range of other measurement and inspection processes. “The result was very favourable. We recorded a value of 3.6 m³/h.m² (v50). By comparison, the EPB assessor had set a target of below 6, while the EPB default value is 12 m³/h.m²,” explains Metifix managing director
Patrick Brants. “We also found virtually no negative airflows from the office spaces. Almost all the air leaks are attributable to the connections with the existing pump room (which houses the building services) and the lifts. In short, the offices themselves come in below 3 m³/h.m², which means we can describe the external envelope of the conditioned volume as ‘very airtight’.”

Patrick Brants: “We recorded a value of 3.6 m³/h.m² (v50). By comparison, the EPB assessor had set a target of below 6, while the EPB default value is 12 m³/h.m².”
High-quality workmanship
However, making its new headquarters so airtight was no mean feat for Cordeel, Patrick Brants emphasises. “It is a very large, open building, with the envelope penetrated at several points (towards the cantilevered floor slabs and the roof). Cordeel therefore decided to use the external wind barrier as an airtight layer as well, and that decision certainly paid off. In addition, the volume can expand on one side (and thus effectively ‘slide’ over one of the two concrete columns), but thanks to the use of the necessary flashings, this has no adverse effect on airtightness either. All this demonstrates that the quality of the workmanship is exceptionally high!”