Acoustics

Acoustic aspects of concrete structures

Bouwconcept met onderbroken vloerplaten en dragende ontdubbelde muren. (Beeld: © WTCB)
Bouwconcept met onderbroken vloerplaten en dragende ontdubbelde muren. (Beeld: © WTCB)

The standard NBN S 01-400-1, ‘Acoustic criteria for residential buildings’, sets out the requirements for completed buildings in terms of airborne and impact sound insulation. A thoroughly revised version of the standard is currently being finalised. Assessing sound insulation is a complex matter. The Belgian Building Research Institute (WTCB) will therefore publish a Technical Information Sheet at the end of 2021, offering solutions in the form of building concepts. Since the weight of a concrete building component is indicative of its acoustic performance, the concrete-related building concepts will specify the surface mass required for floors and walls.

Direct and flanking sound transmission in the case of airborne sound.
Direct and flanking sound transmission in the case of impact sound.

Vibrations in building components travel directly through the air into neighbouring rooms, a process known as direct sound transmission (D). They can also be transmitted through the connections between building components, which is known as flanking sound transmission (F). Sound vibrations in the air in one room are transmitted to other rooms via the surrounding building components. When the components themselves are made to vibrate directly, this is known as impact sound, for example footsteps and knocks. Airborne and impact sound insulation require different approaches. Insulating building components against impact sound transmission usually requires a vibration-damping layer.

Since airborne sound is less able to set heavy building components vibrating than lightweight ones, this source of noise nuisance can be countered simply by increasing the weight of the building component. It should also be noted that most sound transmission takes place through the floor. The weight of the floor assembly therefore plays a particularly important role in determining the level of airborne sound transmission between different rooms.

Indicative minimum thicknesses for hollow-core floor units according to surface mass.

Minimum surface mass 

Acoustic building concepts place considerable emphasis on the minimum surface mass of the floor assembly. The many simulations and calculations carried out in advance show that this is a decisive factor in achieving the desired or required level of sound reduction. For concrete building concepts, sound reduction can be further improved by increasing the weight of the walls or, when using lighter masonry units, by installing acoustic wall strips between them. 

The table below summarises the indicative minimum thicknesses of the floor assembly components when hollow-core floor units are used. The stated surface mass of the load-bearing floor includes any structural topping and the levelling layer beneath the vibration-damping layer of the floating screed. Several combinations are possible to achieve the required minimum surface mass.

For wide slab floors, the required surface mass can easily be converted into a minimum thickness for the wide slabs, together with the in-situ concrete topping and levelling layer. The levelling layer is often a sand-cement screed with a density of 2000 kg/m³. A density of 2500 kg/m³ is assumed for the concrete in the wide slabs and in-situ topping. 

Points to note

Incorrect design, such as insufficient insulation performance of the resilient layer, and the faulty installation of floating screeds, for example the absence of a flexible joint between the skirting board and floor tiles or careless installation of the resilient layer, can compromise both airborne and impact sound insulation. Where acoustic wall strips are required, they must be installed beneath, and possibly above, all load-bearing walls. Compression tests have shown that using acoustic wall strips can reduce the compressive strength of the masonry, depending on the type of block, the type of wall strip and whether a mortar layer is provided between the strips and the first course of blocks. The stability of load-bearing walls on wall strips should therefore be assessed in advance by a structural engineering consultancy.    