Fire spread through the cavity in precast concrete façades

Branddammen kunnen de kans op verspreiding van de brand naar de hogerliggende verdiepingen inperken. (Beeld: Julia Senkevich/Shutterstock)
Branddammen kunnen de kans op verspreiding van de brand naar de hogerliggende verdiepingen inperken. (Beeld: Julia Senkevich/Shutterstock)

Current fire regulations do not set explicit requirements for fire spread via ‘other essential components’ of a façade system. The Superior Council for Fire and Explosion Protection has, however, approved a text on the subject which is expected to be published as law in mid-2022. In the meantime, designers and fire services can use this text as a code of good practice. Precast concrete façade systems generally protect the essential components incorporated in them, provided that the correct detailing is used and the required reaction to fire class for these materials is respected. 

An ‘essential component’ is a material that forms a significant part of a non-homogeneous product. A layer with a mass per unit area of at least 1.0 kg/m² or a thickness of at least 1.0 mm is considered an essential component. This article covers ‘other essential components’, meaning essential components that are not part of the external cladding. In common precast concrete façade systems, this means the insulation.

Precast concrete façade systems with a cavity

This category includes systems in which the façade is constructed from concrete masonry units or overclad façade panels (usually architectural concrete). There is therefore a ventilated cavity between the façade construction and the insulation. As regards the reaction to fire class of the ‘other essential components’, in this case the insulation, there is no requirement for low-rise buildings protected all around by a layer of K210 or EI15. A minimum reaction to fire class of E applies to low-rise buildings (with no additional requirements), medium-rise buildings (provided a standard solution for façade systems with a cavity is used), medium-rise buildings protected all around by a layer of K210 or EI15, and high-rise buildings (provided a standard solution for façade systems with a cavity is used and the building is protected all around by a layer of K230 or EI30). For high-rise buildings (with no additional
requirements), a minimum reaction to fire class of A2-s3,d0 applies.

Medium-rise buildings: standard solutions for façade systems without a continuous cavity.

Precast concrete façade systems without a cavity

This category includes systems in which the façade is constructed from sandwich panels or insulated double walls. These systems have no ventilated cavity between the outer leaf and the insulation. As regards the reaction to fire class of the ‘other essential components’, in this case the insulation, there is no requirement for low-rise buildings protected all around by a layer of K210 or EI15. A minimum reaction to fire class of E applies to low-rise buildings (with no additional requirements), medium-rise buildings (provided a standard solution for façade systems without a cavity is used), medium-rise buildings protected all around by a layer of K210 or EI15, and high-rise buildings (provided a standard solution for façade systems without a cavity is used and the building is protected all around by a layer of K230 or EI30). For high-rise buildings (with no additional requirements), a minimum reaction to fire class of A2-s3,d0 applies.

Explanatory notes on the requirements

According to the tables in NBN EN 1996 (Eurocode 6), 9 cm-thick concrete masonry units meet the EI30 requirement and therefore also EI15. Any façade built using concrete masonry units therefore meets the requirements for using insulation with reaction to fire class E. According to the tables in NBN EN 1992 (Eurocode 2), a concrete wall element (overclad façade, outer leaf of a sandwich panel or double wall) with a thickness of 6 cm or more meets the EI30 requirement and therefore also EI15. All concrete façades used today have an outer leaf with a minimum thickness of 6 cm and therefore meet this requirement.

‘Protected all around’ means on every side: both the internal and external faces, as well as the reveals of all openings, such as windows and doors. The standard solutions will be illustrated in the legislation when it is published. They depend on whether the façade system has a cavity. The standard solutions differ for
medium-rise and high-rise buildings. The principle is to interrupt the ventilated cavity and the insulation with fire barriers to limit the risk of fire spreading to the storeys above. Fire barriers may be required around (or only above) window and door openings, at a specified height and/or at intervals of a set number of storeys.

More information: FEBE, www.febe.be, [email protected]  